1.Working condition of water cooled chiller : inlet temperature of chilled water is 12 ℃,the outlet temperature of chilled water is 7 ℃,the inlet temperature of cooling water is 30 ℃. Working condition of air cooled chiller : inlet temperature of chilled water is 12 ℃,the outlet temperature of chilled water is 7 ℃,the ambient temperature is 35 ℃.
2.The safe working range of the chiller is: the inlet temperature of chilled water is 9-20 ℃.
3. The power supply system is 3ph-380v-60hz, and the allowable voltage fluctuation is ± 10%. The allowable phase to phase voltage difference is ± 2%.
4.The above data is based on the data of refrigerant R22. If R134a, R407C and other working fluids are used, please contact us.